By: Brent Purdy and David Saenz, Automation Direct
Is your facility affected by excessive power prices, frequent nuisance journeys, and repeated asset failures? Energy monitoring could possibly be simply resolution you want. With out knowledge, it’s inconceivable to make knowledgeable selections. In any case, you possibly can’t repair it in the event you can’t see it. Energy displays, or energy high quality analyzers, ship easy, actionable insights.
Energy monitoring can be utilized to establish frequent energy issues. It could actually assist organizations decrease unscheduled downtime, cut back untimely tools failures, and decrease the money and time spent on upkeep. In manufacturing, energy monitoring can be utilized to enhance productiveness and high quality. It could actually assist knowledge heart operators meet service-level agreements. Final, however positively not least, energy monitoring can result in substantial financial savings in total power prices. Whether or not you’re operating a manufacturing facility, a course of facility, or an AI knowledge heart, energy monitoring is an important expertise.
To get a holistic image of a facility’s energy, set up displays/meters at each the distribution (panelboards and switchboards) and on the distributed hundreds (industrial management panels, motor management facilities (MCCs), and drives). Performance varies however gadgets sometimes measure parameters like voltage, frequency, present, lively energy (kW), reactive energy (kVAr), obvious energy (kVA), and energy issue. Meters steadily additionally calculate portions like lively power (+kWh) and reactive power (+kVArh). Many gadgets additionally carry out harmonic evaluation to find out complete harmonic distortion (THD; see Determine 1).
Determine 1: The Socomec DIRIS A20 is a configurable panel-mounted energy meter that provides easy accessibility to key metrics like present, voltage, energy issue, power, and THD.
Energy meters should be put in by an electrician however the course of is easy. These gadgets are typically bundled with software program instruments for ease of configuration. Cloud-based variations can retailer and analyze knowledge off-site for ease of use and distant entry.
Idle/standby power waste
One of many best and only functions of energy monitoring is to establish tools that’s saved operating constantly, even when not performing work. Suppose pumps or followers left on in a single day, or air compressors operating unloaded. Idle/standby power waste is steadily caught by power monitoring throughout audits and might add as much as huge financial savings This represents low hanging fruit that may present some straightforward wins to assist construct momentum for instrumenting extra broadly throughout the ability.
What you see: Important power consumption (kWh) throughout nights/weekends
Corrective actions:
- Implement shutdown procedures for idle tools.
- Add automated controls (timers, occupancy sensors, PLC interlocks, and so on.).
- Use variable frequency drives (VFDs) to match the operation of pumps, followers, and compressors to demand, quite than operating them at prime velocity and utilizing a mechanical valve/choke to regulate output. VFDs can prolong motor lifetime and supply power financial savings when sequenced successfully.
Inrush present on motor startup
Present draw within the first few milliseconds of AC induction motor operation, whereas windings are being energized, could be as much as 10 instances as excessive as steady-state present. Excessive inrush present on massive inductive hundreds can result in voltage sags that may affect different tools all through the ability.
What you see: Excessive present (A) inrush occasions recorded throughout startup
Corrective actions:
- Add comfortable starters or VFDs. These gadgets suppress inrush present, lowering the magnitude of the voltage sag seen by different gadgets.
- Outsized motors, a typical design flaw, draw extreme present. Verify motor specs along with your distributors to make sure that they’re sized appropriately.
Excessive peak demand/load profile spikes
Utilities steadily scale power charges for industrial prospects by most peak demand for a given time interval. Relying on the circumstances, just some load spikes might have an effect on power pricing for a complete quarter.
What you see: Demand graph exhibiting sharp peaks throughout shift begin, motor startups, or batch processes
Corrective actions:
- Stagger tools startup instances.
- Use comfortable starters/VFDs on massive motors to cut back inrush currents.
- Apply demand management techniques to shed or shift non-critical hundreds to off-peak hours with decrease charges.
Poor energy issue (Low PF < 0.9)
Energy issue (PF) is the ratio of the true energy absorbed by the load (kW) to the obvious energy flowing within the circuit (kVA):
[1]
Energy issue is basically a measure of how successfully {an electrical} system converts energy into work. A superb analogy for energy issue is a glass of beer. The entire glass of beer represents the obvious energy – the whole energy equipped by the utility. The beer within the glass represents actual energy – the half that does helpful work (like quenching your thirst). The froth symbolizes the reactive energy – it takes up area within the glass, including to obvious energy, however does no helpful work.
Energy issue is a key metric for assessing effectivity. An influence issue PF < 0.9 implies that {the electrical} system is losing energy, which impacts utility prices in two methods. First, there’s the plain expense of inflated obvious energy, however as well as, utility corporations sometimes assess a surcharge on amenities with energy components beneath a specified degree, to compensate for the price of supplying extreme reactive energy. The decrease the facility issue, the upper the surcharge; relying on the operation, this recurring surcharge could be substantial.
Low energy issue stresses tools, shortening lifetime. It will increase line losses and voltage drop. It could actually additionally trigger transformer heating and result in wasted capability in transformers/cables.
Correcting the issue begins with figuring out it. Energy meters typically provide energy issue performance (see Determine 2).

Determine 2: Along with fundamentals like present and voltage monitoring, the Trumeter ADM100W-HPS graphical energy meter consists of superior features like energy issue, THD, and power monitoring. Modbus connectivity gives expanded studying of knowledge values, like section angle or alarm(s).
What you see: Low energy issue studying as a consequence of inductive hundreds (motors, welding processes, HVAC)
Corrective actions:
- Set up capacitor banks or lively harmonic filters..
- Add synchronous condensers (synchronous motors whose shafts will not be linked to a load) to cancel out lagging PF.
- Use VFDs with lively entrance ends or 12-pulse or 18-pulse rectifiers.
Voltage transients – sags/dips, surges, and swells
The time period voltage transient refers to variations of voltage ranges equipped to a load on account of the startup, shutdown, or operation of one other load on the distribution system. Voltage sags, or dips, are outlined as a drop of 10% to 90% from steady-state voltage. Voltage swells and surges are voltage will increase labeled by length: Voltage surges contain temporary (microseconds to milliseconds) spikes, whereas voltage swells can final for so long as a minute.
Voltage transients can have a wide range of detrimental outcomes starting from nuisance journeys to untimely failure of kit. The injury from voltage spikes, particularly, could be each speedy and in addition cumulative, degrading and damaging tools over time. They’ll additionally cut back product high quality and throughput, impacting OEE.
What you see: Dips when massive motors begin, or spikes when tools shuts off
Corrective motion:
- Add motor comfortable starters or VFD ramping.
- Use uninterruptible energy provides (UPS) for crucial hundreds.
- Set up surge safety gadgets (SPD) on principal panels.
- Upsize transformers or drives to cut back present draw.
- Stage startups of downside tools or diversify feeder circuits for crucial or problematic hundreds.
Harmonics and complete harmonic distortion (THD)
Whole harmonic distortion (THD) refers back to the degradation of an ideal sinusoidal voltage or present waveform on account of higher-order harmonics. THD is successfully a measure of how distorted or “soiled” the facility is with respect to the reference sinusoidal wave. Widespread sources of harmonics embrace nonlinear hundreds equivalent to VFDs, switching energy provides, and LED or fluorescent lighting. This isn’t only a downside for factories. Knowledge facilities are full of nonlinear hundreds, together with servers, UPS, and the VFD-driven AC induction motors that energy the HVAC models.
Excessive THD can result in overheating and untimely failure of property, in addition to unusual habits and untimely failure of delicate tools like PLCs. It could actually additionally lower energy issue and introduce voltage transients. For extra data on THD ranges and their affect on distribution techniques and tools, see IEEE 519.
What you see: Excessive harmonic distortion from drives, servers, UPSs, LED lighting, welders, and so on.
Corrective actions:
- Set up harmonic filters (passive or lively).
- Use 12-pulse or 18-pulse drives the place doable.
- Use Ok-rated or harmonic-mitigation transformers to maintain hundreds which are delicate to excessive THD on devoted circuits.
- Steadiness hundreds by placing nonlinear hundreds and different troublesome property onto completely different circuits.
Voltage imbalance/unbalance
Voltage imbalance refers back to the variations between the section voltages in multi-phase electrical techniques or networks in comparison with the typical voltage. On motors, a voltage imbalance of two% or extra may cause overheated windings, untimely failure, and efficiency degradation equivalent to counter torque. On transformers, unbalanced loading can result in sizzling spots and overheat windings, which can trigger untimely failure. As well as, voltage imbalance can result in present imbalance, an issue in its personal proper.
What you see: Unequal line-to-line voltages (sometimes >2% imbalance)
Corrective actions:
- Redistribute hundreds between phases.
- Examine provide transformers for faucet settings or winding points.
- Repair unfastened or corroded connections.
Present imbalance/overloaded circuits
Present imbalance refers to variations within the section currents for every section of a three-phase system in comparison with the typical. In three-phase motors, present imbalance may cause overheating, torque variations, and untimely failure. However it’s an even bigger downside than that. Within the three-phase energy system operating the ability, even modest present imbalances can increase impartial currents. It could actually create issues throughout the complete facility, for instance overheating panels and transformers, notably if the system already has excessive THD.
IEEE 141 recommends present imbalances of <5% for small industrial amenities and <4% for giant amenities, noting that for some delicate tools, even 2% is an excessive amount of.
Present imbalance has a wide range of causes starting from unbalanced hundreds within the distribution system to unfastened or corroded contacts.
What you see: One section of a three-circuit carries a lot increased present
Corrective actions:
- Rebalance load distribution throughout phases.
- Determine failing motors or drives pulling uneven present.
- Improve wiring or breakers if they’re persistently overloaded.
- Repair unfastened or corroded contacts.
It’s straightforward to imagine that energy points are brought on by the utility and there’s nothing to be carried out about it. In actuality, many energy high quality points, and the complications they create, originate throughout the facility and could be corrected – as soon as they’re recognized. Energy monitoring makes the invisible seen by means of granular knowledge that reveals precisely what’s happening. The insights it delivers can slash power prices by means of eliminating waste peak demand and energy issue penalties. Energy monitoring can assist establish troubled property and stop productivity-killing repeat failures and the expensive downtime they trigger. Most fixes are easy, equivalent to load balancing, filtering, bettering controls, or making tools upgrades like switching to VFDs. From factories to course of industries to the AI knowledge facilities arising all over the world, energy monitoring can enhance effectivity, reliability, and profitability. Discover out extra at wtwh.me/powerquality.
Brent Purdy is product supervisor, and David Saenz is product engineer, for the Energy & Circuit Safety at Automation Direct.
Ideas for Getting Began
- Design energy monitoring techniques into expansions and new builds – it’s simpler to incorporate within the funds upfront.
- For retrofits, search for an inside champion to assist drive the initiative.
- Emphasize that knowledge from meters will cut back unscheduled downtime and velocity troubleshooting within the occasion of failures. This can be utilized to justify the expense of putting in the displays and fixing the system.
- Don’t attempt to instrument the complete flooring abruptly – search for low-hanging fruit the place you may get short-term wins. Examples embrace property that fail steadily, and tools topic to nuisance journeys.
- Conversely, you do want sufficient granularity to acquire actionable insights – one energy meter on the principal may be capable to present a normal downside however received’t assist with troubleshooting.
- Faucet the experience of your distributors and integrators. They’ve guided different organizations by means of this transition.